oolBookedFree tools for HVAC pros

EPA 608 Type I Small-Appliance Specifics

Five pounds, factory-sealed — and recovery rules that exist nowhere else in Section 608.

The short answer

A "small appliance" is not just a small system. Under §82.152 it must be fully manufactured, charged, and hermetically sealed in a factory with 5 pounds or less of refrigerant. Miss any element — field-assembled, field-charged, or over 5 lb — and it is not a small appliance, even if it holds only 4 lb. Recovery from a small appliance is percentage-based, not Table 1-based: 80% or 90% depending on equipment era and whether the compressor runs, or 4 inches of Hg vacuum as the alternative.

The definition, element by element

Section 82.152: "Small appliance means any appliance that is fully manufactured, charged, and hermetically sealed in a factory with five (5) pounds or less of refrigerant." The listed examples: refrigerators and freezers (home, commercial, or consumer use), medical or industrial research refrigeration equipment, room air conditioners (including window air conditioners, portable air conditioners, and packaged terminal air heat pumps), dehumidifiers, under-the-counter ice makers, vending machines, and drinking water coolers.

Recovery: the 80% / 90% rules and the 4-inch alternative

Section 82.156(b) — before opening a small appliance or when disposing of one, recover with a §82.158-certified machine according to one of these:

Equipment eraCompressorRequired recovery
Manufactured before Nov 15, 1993Either80% of the refrigerant (§82.156(b)(1))
Manufactured on/after Nov 15, 1993Functioning90% (§82.156(b)(2))
Manufactured on/after Nov 15, 1993Not functioning80% (§82.156(b)(2))
Any era (alternative to the percentages)EitherEvacuate to 4 inches of Hg vacuum (§82.156(b)(3))

Two exam traps live in this table. First, pre-1993 equipment has no compressor split — it is 80% whether the compressor runs or not. Second, the 4-inch vacuum is a standalone alternative in its own paragraph, not a bonus requirement on top of the percentages. Note what is not here: Table 1's evacuation levels (0/4/10/15 in Hg, 25 mm Hg absolute) apply to appliances except small appliances — Type I recovery is percentage-based by design.

Recovery options that only apply here

After recovery: where the refrigerant may go

Drill it

Type I is the shortest section and the easiest to overthink — the traps are all in the definition and the percentage table.