Digital Ductulator

Size a new duct from airflow and friction rate, or check an existing duct's velocity and friction — on the job site, from your phone. No account, nothing uploaded, nothing stored.

Beta. This tool is live for real-world testing. Size or check a real duct and tell us what to fix — nothing is uploaded or stored.
Two directions, one page. Size a new duct: enter CFM and a friction rate, get the round size (and a rectangular option). Check an existing duct: enter CFM and the size you have, get its velocity and friction rate. Both modes flag noise risk, friction outside the residential band, and bad aspect ratios.

Size a new duct

Residential band 0.08–0.10. Manual D default 0.08.
Flex is rougher, so it sizes larger at the same friction.
What this tool does — and doesn't. It sizes a duct run. It does not design the system: total external static pressure, fittings, and the equipment's rated ESP still govern. A 90° elbow adds roughly 25 ft of equivalent length — fittings, not straight runs, are what usually blow a friction budget. For a whole-house design, do a full ACCA Manual D. Rectangular ducts run roughly 15–25% higher friction than a round duct of the same area — the equivalent diameter below already adjusts for that; keep the aspect ratio under 4:1. Flex duct: pull it tight and support it — compressed or sagging flex is rougher than modeled, so the flex size here is a planning size, not a guarantee. And don't forget the return: sizing the supply and ignoring the return starves the blower even when the supply math looks fine.