EPA 608 Equipment Certification

Certified equipment is a condition of servicing at all — and certification belongs to the machine's model line, not to you.

The short answer

Section 608 makes certified equipment a condition of servicing at all: no one may maintain, service, repair, or dispose of an appliance unless the recovery/recycling equipment used is certified under §82.158 and used in accordance with the manufacturer's directions (§82.154(b), §82.156(g)). The certification belongs to the machine's model line, not to the technician — and a machine that no longer meets the standard no longer counts as certified, however good it was when new.

What “certified” means, by equipment era

Table 2: what certified equipment must be able to pull

Table 2 (§82.158) mirrors Table 1's evacuation levels, including the low-pressure row: 25 mm Hg absolute in both equipment columns. A machine certified for high-pressure work is not automatically certified for low-pressure work — the label's appliance category is what counts, and §82.156(a) requires equipment certified for that refrigerant and appliance.

When a machine stops being certified — and must be repaired or retired

Built-in requirements: purge devices and low-loss fittings

Leak-checking your equipment: what the rule says, and what it doesn't

The CFR sets no technician leak-check interval for recovery equipment — there is no “check it every X days” rule in §82.158 to quote, and this page does not invent one. What the framework does require, in substance, is that the machine you use is certified and performs to its standard: a machine leaking refrigerant at its fittings is not achieving its evacuation level and is not being used as its certification assumes. Exam-prep materials teach checking the recovery device for refrigerant leaks as routine maintenance — treat that as sound practice and likely exam content, but as practice, not a CFR interval. If a question asks for a CFR-mandated check frequency for recovery equipment, the honest answer is that the CFR does not set one; the 3-year figure belongs to manufacturer retesting (§82.158(i)), not to your pre-job check.

Two scope limits worth knowing

Drill it

Equipment questions hide in every bin — Type I tests the small-appliance percentages, Type II the Table 1/2 levels. Run both, then the scenarios.