EPA 608 Recovery Cylinder Rules

The 80% fill limit, DOT ratings, labeling, and the never-mix rule — the cylinder rules Type I, II, and III all test.

The short answer

Recovered refrigerant goes only into a DOT- or UL-standard recovery cylinder, filled to no more than 80% of its rated volume, labeled with the refrigerant it contains, and never mixed with another refrigerant. Everything on this page is the field version of rules that sit in the 40 CFR Part 82 recovery-equipment appendices, DOT cylinder standards, and long-standing industry practice — the page says which is which, because the exam tests the numbers, not the footnotes.

The 80% fill limit

Recovery equipment must provide overfill protection so that a storage container's liquid fill does not exceed 80% of the tank's rated volume at 21.1 °C (70 °F), per DOT standards (49 CFR §173.304) as referenced in the Part 82 equipment appendices. The headroom is for thermal expansion: liquid refrigerant expands as it warms, and a liquid-full cylinder has nowhere for that expansion to go.

DOT ratings, markings, and retesting

Portable refillable tanks used with recovery equipment must meet applicable Department of Transportation (DOT) or Underwriters Laboratories (UL) standards (Part 82 equipment appendices). In the field that means:

Labeling: what goes on the cylinder

When a cylinder containing used refrigerant is shipped or sent for reclamation, DOT labeling must identify the refrigerant inside. Labeling serves three purposes the exam likes to ask about: it prevents accidental mixing, it lets the reclaimer identify the contents, and it supports the recordkeeping the rules require. As a working habit, label at the moment of recovery — not when the truck is loaded — with at least the refrigerant type.

Color is a convention, not the label. Recovery cylinders are conventionally gray with a yellow top, which distinguishes them from virgin-refrigerant cylinders (whose colors vary by refrigerant). Color helps you grab the right cylinder; the written label is what the shipment and the reclaimer rely on. A2L cylinders add their own scheme — gray body with a red band marking a flammable refrigerant — covered on the safety-classes page.

Never mix refrigerants in one cylinder

One refrigerant per recovery cylinder, no exceptions in the field. A mixed charge cannot be separated by ordinary recovery or recycling equipment, so it generally cannot be reclaimed and becomes destruction-only material. That is also why recovered refrigerant may be returned, without recycling or reclaiming, only to the appliance it came from or to another appliance owned by the same person (§82.156(h)) — the rule assumes the refrigerant's identity is known and unmixed.

Storage and transport habits

Drill it

Cylinder rules show up in Core and again in every Type section. Run the safety and cylinders bin, then take the mixed exam.