EPA 608 Evacuation Levels

Table 1, both equipment columns — the table Type II and Type III are built on.

The short answer

Before a non-small appliance is opened for major work, it must be evacuated to the level in EPA's Table 1 (40 CFR §82.156). The number depends on the appliance's pressure class, its charge size, and whether the recovery equipment was made before or after November 15, 1993. Low-pressure appliances are the odd row out: 25 mm Hg absolute, either era.

Table 1 — required levels of evacuation

Appliance typeEquipment made before Nov 15, 1993Equipment made on/after Nov 15, 1993
Very-high-pressure appliance0 in Hg0 in Hg
High-pressure appliance (or isolated component), full charge under 200 lb0 in Hg0 in Hg
High-pressure appliance (or isolated component), full charge 200 lb or more4 in Hg10 in Hg
Medium-pressure appliance (or isolated component), full charge under 200 lb4 in Hg10 in Hg
Medium-pressure appliance (or isolated component), full charge 200 lb or more4 in Hg15 in Hg
Low-pressure appliance25 mm Hg absolute25 mm Hg absolute

All values are inches of Hg vacuum relative to standard atmospheric pressure (29.9 in Hg), except the low-pressure row, which is absolute. Pressure classes are defined in §82.152 by the refrigerant's saturation pressure at 104 °F: very-high (critical temperature below 104 °F, or above 355 psia), high (170–355 psia), medium (45–170 psia — R-134a lives here), low (below 45 psia — R-11, R-123, R-113, R-245fa).

The rules around the table

Drill it

Table 1 is the most-tested table in Type II and Type III. Run the bins, then take the mixed exam.